Specialized Container House

Background Introduction

In recent years, container houses, which were originally used for transporting heavy goods, have gradually been repurposed by architects for applications such as cafes and boutique hotels due to their advantages of low cost, high strength, durability, and recyclability, especially with the loosening of construction regulations. Internationally, container houses have long been used for hazardous chemical storage facilities and emergency shelters for personnel.

The need for hazardous chemical storage and emergency shelters for personnel has always been a crucial aspect in many industries. However, storing these chemicals or providing emergency shelters involves a series of safety risks, with fire and explosion being among the most common. To address these challenges, Liansuo Construction Technology has modified container houses, categorizing the products into fireproof, explosion-proof, flame-resistant, and personnel shelter types for hazardous chemical storage and emergency sheltering. These products ensure employee safety, prevent environmental pollution, and protect property from damage while adhering to safety and compliance standards for customers.

References to Domestic and International Standards

  • CNS11227-1: Fire Resistance Test Method – Part 1: Door and Rolling Door Components
  • CNS6532: Fire Resistance Test Method for Building Interior Materials
  • CNS12514-8: Fire Resistance Test Method for Non-Load-Bearing Exterior Walls
  • CNS12514-5: Fire Resistance Test Method for Floors and Roof Components
  • CNS12514-1: Fire Resistance Test Method for Building Structural Components – Part 1
  • CNS941: Steel Cable Load Testing
  • Standards for the Establishment and Safety Management of Manufacturing and Storage Facilities for Hazardous Substances and Combustible High-Pressure Gases
  • FM 1-44: Damage-Limiting Construction (Datasheet)
  • FM6049: FM Approval Standard for Flammable Liquid Storage Buildings and Lockers
  • FM4440: FM Approval Standard for Explosion Venting Systems Including Fasteners and Latches for Damage-Limiting Construction
  • NFPA 30: Flammable and Combustible Liquids Code

LS-20GP01 Chemical Container House (Fireproof Type) Product Technical Specifications

No.Part NameMaterialTechnical Parameters
1Roof/WallCorrugated steel panel + stamped metal composite panel (thickness 9.5mm; electrostatic powder coating) + rock wool (128K) + ceramic wool (128K) + square steel tube (100*100*3mm)Wall thickness: 140mm; Fire resistance: ≥3 hours (CNS12514-5); Explosion resistance: ≥4.8kPa (FM1-44)
2FloorStamped metal composite panel (electrostatic powder coating)Flame resistance: Class 1 (CNS6532)
3FrameGalvanized steel pipe + electrostatic powder coatingStructural strength meets FM6049 requirements
4Fireproof and Explosion-proof DoorSteel (Width: 2114mm * Height: 2231mm)Fire resistance: ≥2 hours (CNS11227-1)
5FoundationSpecial fixed deviceC30 concrete / thickness: 100-200mm
6Dimensions20-foot container house6058 * 2438 * 2591mm

LS-20GP02 Chemical Container House (Explosion-proof Type) Product Technical Specifications

No.Part NameMaterialTechnical Parameters
1WallCorrugated steel panel + stamped metal composite panel (thickness 9.5mm; electrostatic powder coating) + rock wool (128K) + ceramic wool (128K) + square steel tube (100x100x3mm)Wall thickness: 140mm; Fire resistance: ≥3 hours (CNS12514-5); Explosion resistance: ≥4.8kPa (FM1-44)
2RoofCorrugated steel panel + reinforced cement fiberboard (9mm) + rock wool + square steel tube (100*100*3mm)
3Roof Explosion VentLS explosion vent Panel ; FM-certified vent fastener/LS-EV01damage force value: 700N; explosion vent pressure: 0.96kPa-1.92kPa
4FloorStamped metal composite panel (electrostatic powder coating)Flame resistance: Class 1 (CNS6532)
5FrameGalvanized steel pipe + electrostatic powder coatingStructural strength meets FM6049 requirements
6Fireproof and Explosion-proof DoorSteel (Width: 2114mm * Height: 2231mm)Fire resistance: ≥2 hours (CNS11227-1); Explosion resistance: ≥4.8kPa (FM1-44)
7 FoundationSpecial fixed deviceC30 concrete / thickness: 100-200mm
8Dimensions20-foot container house6058 * 2438 * 2591mm

LS-20GP03 Chemical Container House (Flame-resistant Type) Product Technical Specifications

No.Part NameMaterialTechnical Parameters
1Roof/WallCorrugated steel panel + stamped metal composite panel (thickness 9.5mm; electrostatic powder coating) + rock wool (128K) + square steel tube (100*100*3mm)Wall thickness: 130mm
2 FloorStamped metal composite panel (electrostatic powder coating)Flame resistance: Class 1 (CNS6532)
3FrameGalvanized steel pipe + electrostatic powder coatingStructural strength meets FM6049 requirements
4FoundationSpecial fixed deviceC30 concrete / thickness: 100-200mm
5Dimensions20-foot container house6058 * 2438 * 2591mm

LS-20GP04 Personnel Shelter (Explosion-resistant Type) Product Technical Specifications

No.Part NameMaterialTechnical Parameters
1Roof/WallCorrugated steel panel + stamped metal composite panel (thickness 9.5mm; electrostatic powder coating) + rock wool (128K) + ceramic wool (128K) + square steel tube (100*100*3mm)Wall thickness: 140mm; Fire resistance: ≥3 hours (CNS12514-5); Explosion resistance: ≥4.8kPa (FM1-44)
2FloorStamped metal composite panel (electrostatic powder coating)Flame resistance: Class 1 (CNS6532)
3FrameGalvanized steel pipe + electrostatic powder coatingStructural strength meets FM6049 requirements
4Fireproof and Explosion-proof DoorSteel (Width: 2114mm * Height: 2231mm)Fire resistance: ≥2 hours (CNS11227-1)
5FoundationSpecial fixed deviceC30 concrete / thickness: 100-200mm
6Dimensions20-foot container house6058 * 2438 * 2591mm